ECTS2 Series IEC Harmonics & Flicker Test Systems.
The Pacific Power Source EMC Compliance Test Systems use a sophisticated Harmonics and Flicker measurement system and newly designed flicker impedance options to support single and three phase IEC 61000-3 AC harmonics, flicker as well as IEC 61000-4 AC and DC immunity compliance testing of EUTs up to the maximum required current of 75A per phase.
This series consists of several system configurations to accommodate both single and three phase compliance testing at a wide range of power levels. All ECTS2 systems use the same IEC 61000-3 Harmonics and Flicker Emissions and IEC 61000-4 Immunity test software.
For compliance testing of Renewable Energy products like Solar and Wind Inverters or AC Grid connected Electric Vehicle Charging systems, the AZX based ECTS2 system configuration support full energy recycling to the utility grid.
Electronic Power Transfer Switch Options
Also see EPTS Series IEC61000-4-11 & -4-34 Voltage Dips, Interruptions & Variations Test options
The ECTS2 Series of Harmonics and Flicker Test System allows EMC labs and manufacturers to perform full compliance testing of products to the following IEC standards:
IEC 61000-3-2 Harmonics and Inter Harmonics to 16A/phase
IEC 61000-3-12 Harmonics and Inter Harmonics to 75A/phase
IEC 61000-3-3 Flicker to 16A/phase
IEC 61000-3-11 Flicker to 75A/phase
IEC 61000-4-11 AC Voltage Dips, Interruptions and Variations to 16A/phase
IEC 61000-4-13 Interharmonics
IEC 61000-4-14 AC Voltage Fluctuations
IEC 61000-4-17 DC Ripple
IEC 61000-4-27 AC Voltage Unbalance three phase
IEC 61000-4-28 Frequency Variations
IEC 61000-4-29 DC Voltage Dips, Interruptions and Variations
IEC 61000-4-34 AC Voltage Dips, Interruptions and Variations to 75A/phase
The ECTS2 systems provide a comprehensive and cost effective solution for all of your EMC compliance testing needs!
Key Features for Power Line Compliance Testing
- Harmonics and Flicker Emissions Test (IEC 61000-3-XX)
- Power Line Immunity Test (IEC 61000-4-XX)
- AC only or AC and DC Test Systems
- Fully Regenerative Configurations Available (ECTS2-Z)
- Single Phase and Three phase Output Modes
- Programmable Frequency
- Current and Power Limit Protection
- EMC Test Software for Harmonics, Flicker and Immunity
- Detailed test reports to documents EUT compliance
- Wide Range of Power Levels Available
- Lumped Flicker Impedance for Flicker Testing
- Up to 0-600 VAC L-N / 1000V L-L Output Voltage available
- Up to 425Vdc output and 950Vdc Voltage
- 15-1200 Hz Full Power Bandwidth
- USB, LAN, GPIB & RS232 Interfaces
- Transfer Switch Option for IEC 61000-11,-34 and -29
- Choice of Cabinet Sizes
IEC 61000-3-2 & IEC 61000-3-12 Harmonics and Inter Harmonics Emissions Test
The ECTS2 Harmonics and Interhamonics measurement system and associated EMC Software suite meets all requirements for compliance testing to these Harmonics standards.
IEC 61000-3-3 & IEC 61000-3-11 Flicker Emissions Test
The ECTS2 Flicker measurement system and lumped flicker impedance meets all requirements for compliance testing to these Flicker standards.
IEC 61000-4-11, IEC61000-4-27, IEC 61000-4-29, IEC 61000-4-34
When combined with the optional EPTS Power transfer switch, the ECTS2 test system meets the requirement for AC and DC Voltage Dip testing.
IEC 61000-4-13 Inter Harmonics Testing
Optional Inter Harmonics Generator for AMX or AFX based ECTS2 systems supports testing to IEC 61000-4-13
IEC 61000-4-14, IEC 61000-4-17, IEC 61000-4-28
AC immunity tests support for these standard available on LMX based ECTS2 Systems. AC and DC immunity tests support for these same standards are available on AFX based ECTS2 Systems.
Model Comparison - Single Phase Models
Model | Rated Power (VA) | Voltage Max (L-N) (Vrms) | Rated Current Max (Arms) @ 230Vac | Output Frequency (Hz) | Phase Mode Output | Cabinet Height (U) |
---|---|---|---|---|---|---|
ECTS2-108M-x | 750 | Direct: 135/270 | 3.0 | 15-5000 | 1Ø | Option -A |
ECTS2-140M-x | 4000 | Direct: 135/270 | 16 | 15-5000 | 1Ø | 18U |
ECTS2-160M-x | 6000 | Direct: 135/270 | 16 | 15-5000 | 1Ø | 18U |
Model Comparison - Three Phase Models
Model | Rated Power (VA) | Voltage Max (L-N/L-L) (Vrms) | Current Max @ 230Vac (Arms) | Output Frequency (Hz) | Phase Mode Output | Cabinet Height (U) | ||
---|---|---|---|---|---|---|---|---|
ECTS2-360F-x | 6kVA | 1Ø: 333 3Ø: 333/576 | 1Ø: 26 3Ø: 8.7 | 15-1200 | 1, 2, 3 | 18 | ||
ECTS2-3120F-x | 12kVA | 1Ø: 333 3Ø: 333/576 | 1Ø: 52.2 3Ø: 17.4 | 15-1200 | 1, 2, 3 | 18 | ||
ECTS2-3150F-x | 15kVA | 1Ø: 333 3Ø: 333/576 | 1Ø: 65 3Ø: 21.7 | 15-1200 | 1, 2, 3 | 18 | ||
ECTS2-2400F-x | 24kVA | 1Ø: 333 3Ø: 333/576 | 1Ø: 104.3 3Ø: 34.8 | 15-1200 | 1, 2, 3 | 18 | ||
ECTS2-3300F-x | 30kVA | 1Ø: 333 3Ø: 333/576 | 1Ø: 130 3Ø: 43.3 | 15-1200 | 1, 2, 3 | 18 | ||
ECTS2-3300Z-x Regenerative | 30kVA | 1Ø: 360 3Ø: 360/624 | 1Ø: 130 3Ø: 43.5 | 15-1000 | 1, 2, 3 | 34 | ||
ECTS2-3450F-x | 45kVA | 1Ø: 333 3Ø: 333/576 | 1Ø: 195 3Ø: 65 | 15-1200 | 1, 2, 3 | 28 | ||
ECTS2-3550Z-x Regenerative | 55kVA | 1Ø: 360 3Ø: 360/624 | 1Ø: 195 3Ø: 75 | 15-1000 | 1, 2, 3 | 34 | ||
ECTS2-3750F-x | 75kVA | 1Ø: 333 3Ø: 333/576 | 3Ø: 108 | 15-1200 | 2, 3 | 2 x 36 | ||
ECTS2-3900F-x | 90kVA | 1Ø: 333 3Ø: 333/576 | 3Ø: 130 | 15-1200 | 2, 3 | 2 x 36 | ||
ECTS2-31100Z-x Regenerative | 110kVA | 1Ø: 360 3Ø: 360/624 | 3Ø: 150 | 15-1000 | 2, 3 | 2 x 34 |